This professional air cooled water chiller delivers stable and efficient cooling performance for diverse industrial production scenarios. Designed as
Industry Special Machine, it fits perfectly into various precision processing workflows with reliable cooling output. Adopting
Automatic Type operation mode, the unit realizes intelligent temperature regulation and unattended stable running, effectively cutting manual operation costs. Apart from core cooling advantages, it also supports flexible matching with
Others auxiliary supporting equipment, featuring compact structure, low energy consumption and easy installation. It runs steadily in long-term working conditions, ensuring consistent cooling effect to safeguard smooth progress of industrial production.
Model Item | AC-05 |
| Cooling Capacity | kcal/h | 13046 |
| KW | 15.17 |
| Input power | KW | 5.23 |
| Power Supply | 3PH~440V/50HZ |
| Refrigerant | Model | R22 |
| Control type | Expansion valve |
| Compressor | Type | Hermetic scroll type |
| Power | kw | 4.1 |
| Condenser | Type | High effective copper pipes lovered into aluminllm fins+low noise rotor fan |
| Power | kw | 0.38 |
| Cooling air Flow | m3/h | 5000 |
| Evaporator | Type | Water tank with coil |
| Refrigerated Water Flow | m3/h | 2.62 |
| Water Tank Capacity(L) | 60 |
| Inlet and Outlet pipe caliber | 1″ |
| Water Pump | Power (KW) | 0.75 |
| Lift(M) | 20 |
| Safety Protection | Compressor superheating protection, Overcurrent protection, High and low pressure protection, Over temperature protection, Phase sequence/ Phase-lacking protection, Exhaust over heating protection |
| Weight of the Machine | KG | 175 |
| MEAS. | MM | 1140*560*1040 |
Note: 1. The cooling capacity is according to:
Refrigerated water inlet and outlet temperature 17ºC/12ºC; Cooling water inlet and outlet temperature 30ºC/35ºC
2. Working Range:
The temperature range of Refrigerated water is from 5ºC to 35ºC; The inlet and outlet temperature difference is from 3ºC to 8ºC.
The temperature range of cooling water is from 18ºC to 35ºC; The inlet and outlet temperature difference of cooled water is from 3.5ºC to 10ºC.
We reserve the right to change the above dimensions or parameters without further notice. 